Skip to content
Boiler Chemicals

Multi Functional Boiler Treatment

Product code RXSOL-42-5001-025

Highly effective multi-functional liquid reagent for the treatment of steam production systems and heating systems operating on softened water.

Description
More about RXSOL NEUTRALIZER for Boiler System RXSOL-42-5001-025
RXSOL-42-5001-025 is a highly effective multi-functional liquid reagent for the treatment of steam production systems and heating systems operating on softened water.
Application
Application
RXSOL-42-5001-025 contains an antiscalant (phosphate-polymer composition), a mixture of complexones, a pH correction reagent, an oxygen reducer and neutralizing amines. A specially selected composition of phosphates and polymers effectively prevents the formation of deposits throughout the steam production system, preventing the formation of hardness crystals and dispersing suspended particles and iron. The action of polymers is enhanced by complexons, which also form complexes with metal cations in the makeup water and provide online cleaning of the system. The reagent contains components for correcting the pH of feed water.  

The dosage rate is dependent on bioler operating condition, feed 2-3 ltrs of RXSOL-42-5001-025 solution for per thousand ltr of bioler water then control the system by periodic Alkalinity test procedure. If p-Alkalinity is below 200 ppm increase the ratio of RXSOL BWT 5001 solution. If p-Alkalinity is above 400 ppm reduce the concentration of RXSOL-42-5001-025 solution by dilution with water. RXSOL-42-5001-025 is strongly alkaline.RXSOL-42-5001-025  is best applied heat or diluted with any convenient strength on a continuous basis using a suitable chemicals pump. The product should be applied to the boiler feed tank or feed line to ensure adequate mixing.

Precautions
Precautions

RXSOL-42-5001-025 Boiler Water treatment specialized is a well - balanced blend for boiler water treatment products, Resulting Multi Functional Boiler Treatment including scale and corrosion control by one shot operation. A one-step treatment to control the formation of rust and scale in low pressure and auxillary boilers with working pressure up to 20 bars.

The stability of the added polymers are very useful for water treatment processes. Such polymers with low molecular weights cannot only inhibit calcium, magnesium, and silica scale in cooling towers and boilers, but also help corrosion control by dispersing iron oxide. 


Basic Boiler System Schematic

Below is a summary of problems associated with the common impurities in water and solutions to each problem.

List Of Problems Caused By Impurities In Water

Impurity (Chemical Formula)

Problems

Common Chemical Treatment Methods

Alkalinity (HCO3-, CO32- and CaCO3)

Carryover of feedwater into steam, produce CO2 in steam leading to formation of carbonic acid (acid attack)

Neutralizing amines, filming amines, combination of both, and lime-soda.

Hardness (calcium and magnesium salts, CaCO3)

Primary source of scale in heat exchange equipment

Lime softening, phosphate, chelates and polymers

Iron (Fe3+ and Fe2+)

Causes boiler and water line deposits

Phosphate, chelates and polymers

Oxygen (O2)

Corrosion of water lines, boiler, return lines, heat exchanger equipments, etc. (oxygen attack)

Oxygen scavengers, filming amines and deaeration

pH

Corrosion occurs when pH drops below 8.5

pH can be lowered by addition of acids and increased by addition of alkalies

Hydrogen Sulfide (H2S)

Corrosion

Chlorination

Silica (SiO2)

Scale in boilers and cooling water systems

Lime softening